FIRE-LITE ES-200X Fire Alarm Control Panel
Contact us for price breaks on large quantities!
The Fire-Lite ES-200X is a 198-point addressable fire alarm control panel that features a built-in dual path communications, programmable buttons and support for combined fire and CO addressable detection. Compatible with Fire-Lite’s devices in LiteSpeed and CLIP mode; Compatible with legacy Fire-Lite 300 Series devices in CLIP mode only. The control panel provides four Class B or four Class A NACs (Notification Appliance Circuits). Each circuit is capable of 2.5 amps of current. NAC power expandable by 3.0 amps with optional PWRMOD24 module.
Specifications
| Weight | 16 lbs | 
|---|---|
| Dimensions | 8.5 × 22.50 × 20.00 in | 
| Manufacturer | 
    Honeywell  | 
  
| Brand | 
    Fire-Lite  | 
  
| Condition | 
    New  | 
  
| Type | 
    Control Panel  | 
  
| Style | 
    Addressable  | 
  
| Color | 
    Red  | 
  
| Production Status | 
    Active  | 
  
| Compatibility | 
Features
- Listed to UL Standard 864, 10th edition
 - Pre-installed IPOTS-COM Ethernet IP and POTS (Plain Old Telephone Service) Central Station Communicator over AlarmNet
 - Optional CELL-MOD or CELL-CAB-FL GSM Central Station
 - Communicator over AlarmNet®
 - Automated activation of the ECC-50/100 Emergency Command Center
 - ECC-FFT Firefighter Telephone option
 - Compatible with SWIFT® wireless devices
 - Auto-programming (learn mode) reduces installation time. Reports two devices set to the same address
 - Four built-in, independently programmable Style Z (Class A) or Style Y (Class B) NAC circuits
 - Selectable strobe synchronization for System Sensor, Wheelock, and Gentex devices
 - Notification Appliance Circuit End of Line resistor matching
 - Four programmable function keys for ease of maintenance
 - Two programmable relays and one fixed trouble relay
 - Built-in Programmer
 - Integral 80-character LCD display with backlighting
 - Real-time clock/calendar with automatic daylight savings control
 - History file with 1,000 event capacity
 - Addressable sounder base compatibility
 - Multi-criteria detector (smoke, heat, CO) with programmable response
 - Control module delay timer
 - Automatic detector sensitivity testing (NFPA 72 compliant)
 - Automatic device type-code verification
 - Point trouble identification
 - Waterflow selection per module point
 - Alarm verification selection per detector point
 - Maintenance alert warns when smoke detector dust accumulation is excessive
 - One-person audible or silent walk test with walk-test log and printout
 - System alarm verification selection per detector point
 - PAS (Positive Alarm Sequence) and Pre-signal per point (NFPA 72 compliant)
 - Up to 16 ANN-BUS annunciators- 8 per each ANN-Bus
 - Remote Acknowledge, Alarm Silence, Reset and Drill via addressable modules or remote annunciator
 - Upload/Download of program and data via USB with optional FS-Tools Programming Utility